Air Force
Instruction 32-1065
1 October 1998
Civil
Engineering
Grounding Systems
Overview
1.
Compliance with this publication is mandatory.
2.
This instruction implements AFPD 32-10, Installations and
Facilities.
3.
This instruction also implements DOD 6055.9 STD, Ammunition
Explosives Safety Standards
4.
This instruction assigns maintenance responsibilities
5.
Base Civil Engineers are responsible for Ground Resistance
Tests and for 29 of the 34 listed items.
General Facility Resistance Check 25 ohms max every 5 years
POL Facilities Resistance Check 10,000 ohms max when damaged
Tightness
on ground conductors quarterly
Communication
Facilities Resistance Check 10 ohms max every
21 months
Explosive Area Conductive Floor AFMAN 91-201 every 6 months
Hazardous
Explosive Area Resistance Check 25 ohms max except loop every 24 months
Non Hazardous Continuity Check 1 ohm every 24 months
Static
Bar Check 1 ohm every 24
months
Protective Aircraft
Shelter (PAS) Resistance Check every
24 months
Medical Facilities Resistance Check 25 ohms max every
5 years
Airfield Lighting Resistance Check 25 ohms max every 2 years
PMEL Resistance Check 25 ohms max every
2 years
6.
Users are responsible for seven of the 34 listed items but no
Ground Resistance Tests.
Communication
Facilities In House Electronic Ground by
user
Explosive Area Visual Check
Hazardous Static Ground Check 1 ohm by
user each day
Continuity
Check
From Equipment
to
Static bar 1 ohm every 3
months
Or
by T.O,
Explosive Area Visual Check Quarterly
Non Hazardous Static Ground Check 1 ohm every
24 months
Fuel Labs Visual Check Monthly
Of
ground wires
Fuel Labs Visual Check Monthly
Facility
Grounds
7.
Records keeping:
Sketch of the grounding system, test points, date, tester’s name,
general condition of air terminals, conductors, other components,
corrosion protection measures, security
of attachments, resistance measurements, variations from requirements,
discrepancies noted and corrective action, date of repairs. Keep these records for a minimum of 6
inspection cycles.
8.
Visual inspection of the lightning protection system: The
system is in good repair, no loose connections, no excessive corrosion,
conductors are in tact, no excessively frayed wires, no mower damaged wires or
masts, components are securely fastened, surge suppression devices installed
and operational.
9.
Visual inspection of facility grounds: The system is in good repair, no loose
connections, system neutral is grounded at the service entrance including
connection to the grounding electrode, separately derived systems are properly
grounded, flashover protection is installed, grounding systems within the
facility are bonded together at ground level or below.
10.
Static Protection: 13.1.2 Static grounding system must be connected to
the facility grounding system.
11.
Lightning Protection Systems: 14.1 General, streamer emission
systems or charge dissipation systems are not permitted. 14.2
Adequate bonding is more important than grounding. 14.3
Low resistance is desirable but not essential for lightning
protection. For most facilities,
resistance to ground should be less than 25 ohms. If this cannot be achieved where only ground rods are used,
install a ground loop conductor. The
resistance to ground of a ground loop is acceptable even if greater than 25
ohms.
12.
Surge Protection: Metallic power lines, intrusion detection,
communication antenna and instrumentation lines must have surge protection
sized for lightning surges to reduce the transient voltages to a harmless
level. These lines must enter the
facility in shielded cables or metallic conduits run underground for at least
50 feet from the facility. The antenna
leads from antennae on the facility and within the zone of protection do not
have to go underground.
13.
Definition of Facility Ground System: The electrically
interconnected system of conductors and conductive elements that provides
multiple current paths to earth. The
facility ground system can include the earth electrode subsystem, lightning
protection subsystem, signal reference protection subsystem, fault protection
subsystem, static ground subsystem, as well as the building structure,
equipment racks, cabinets, conduit, junction boxes, raceways, duct work, pipes,
and other normally non-current-carrying metal elements.
14.
Definition of Lightning Protection System: A complete system
consisting of components such as air terminals, interconnecting conductors,
ground terminals, surge suppression devices, and other connectors or fittings
and subsystems required to assure a lightning discharge will be safely
conducted to earth.
15.
Attachment 2: Basic Requirements for Grounding Systems. A2.1.6
Static Grounds, Equipment Grounds, Electrical System Grounds, Lightning
Grounds, Signal Reference Grounds are the five basic types of grounding
systems. Each of the grounding systems
may be a subsystem of a total facility grounding system. All grounds and subsystem grounds must be
bonded together according to NFPA 780.
16.
A2.2.1 Ground rods must be at least 8 feet in length and no
closer than 6 feet from other rods or plates.
17.
A2.3.2. Methods of Obtaining Better Grounds: Deeper Rod, Parallel Ground Rods spaced the
distance of the rod as a minimum, Soil Replacement, Concrete Encapsulation,
Extensive Wire Networks, Ground Loop Conductor.
18.
A3.6.4 Fences and railroad tracks within 6 feet of a
structure’s lightning protection system must be bonded to the structure
grounding system.
19.
A4.1.1 Air terminals must extend at least 10 inches above the
object to be protected.
20.
A4.1.4 Lightning protection down conductors must present the
lease impedance to ground.
21.
A4.1.5 Down conductors must not have sharp bends or
loops. All bends must have a radius of
8 inches or greater and measure not less than 90 degrees from the inside of the
bend.
22.
A4.1.8 If a down conductor runs through a ferrous metal tube
of pipe usually for mechanical protection, the conductor must be bonded to both
ends of the tube.
23.
A4.1.9 Do not paint down conductor connectors unless they are
the high-compression or exothermic welded type. Conductors on roots must be bare.
24.
A4.1.11 Ground rods for lightning protection must be at least
10 feet in length and ¾” diameter.
Stainless steel ground rods may not be used. Ground rods must be at least 3 feet from the building walls or
footings and must penetrate 10 feet into soil. Ground rods should be buried at
least 1 foot below grade.
25.
A4.1.15 Ground loop conductors (cable) must not be less than
AWG No. 1/0 copper.
26.
A6.1 Grounding System
Resistance Test. Resistance should be
less than 25 ohms (10 ohms for communication facilities).